ExTox ET-1D(A) — gas detection control unit (1 channel)

The ExTox ET-1D(A) is a single-channel gas detection control unit for flammable, toxic gases and oxygen, working with one 4-20 mA transmitter — e.g. from the ExTox ExSens/Sens range. It has all the functions of the 8-channel ET-8D control unit, limited to a single measuring point: 2 independently adjustable alarm thresholds, 4 potential-free relays, a backlit LCD display and full configuration from the device itself, with no need for a computer.

Key features

  • 1 measuring input, 4-20 mA (microcontroller with A/D converter).
  • Backlit, 4-line LCD display with a concentration bar graph.
  • Green operation LED, 2 red alarm LEDs (level 1 and 2), yellow device/transmitter fault LED.
  • Configuration menu operated from the device keypad — no additional software needed, password-protected.
  • 2 independently adjustable alarm thresholds (upper or lower exceedance), with configurable alarm latching.
  • 4 potential-free relays (230 V / 5 A, max. 10 A total) — alarm 1, alarm 2, fault, siren.
  • 2 potential-free digital inputs.
  • 4-20 mA analogue output (ET-1DA version only).
  • Zero and sensitivity adjustment of the measuring channel, alarm inhibit in service mode, separate acknowledgement of the acoustic alarm.
  • 230 V AC or 24 V DC power supply, selectable; wall, DIN-rail, 19" cabinet or panel mounting — depending on the housing version.

Technical specifications

ParameterValue
Typegas detection control unit — single-channel controller (works with an external transmitter)
Number of channels1 (4-20 mA input)
Gases measurednot applicable — control unit/controller with no sensor of its own; works with flammable-, toxic-gas and oxygen transmitters (e.g. ExTox ExSens/Sens)
Signal input1× 4-20 mA
Analogue output4-20 mA (ET-1DA version only)
Digital inputs2× potential-free
Relays4× potential-free changeover contacts, 230 V / 5 A (max. 10 A total) — alarm 1, alarm 2, fault, siren
Alarm thresholds2, independently configurable, with alarm latching
Indicationbacklit 4-line LCD display, operation LED (green), 2 alarm LEDs (red), fault LED (yellow)
Power supply230 V AC or 24 V DC (selectable)
Power consumption20 W (230 V AC max. 0.08 A; 24 V DC max. 0.8 A)
Operating temperature-10°C to +40°C
Storage temperature-25°C to +60°C, humidity non-condensing
Housing versions / dimensionswall-mount 160×194×90 mm (IP54); panel-mount 296×196×80 mm (indicator module) + 160×160×40 mm (I/O strip); DIN-rail and 19" cabinet versions also available
Protection ratingIP54 (wall-mount housing)
Approvals / ATEXcompliant with EN 60079-29-1, EN 45544-1 to -3, EN 50104; directives 2014/34/EU (ATEX), 2014/30/EU (EMC), 2014/35/EU (LVD)
Pumpnot applicable — control unit/controller, does not sample air
Connectivitywired, 4-20 mA input from the transmitter; 4-20 mA output to the higher-level system (ET-1DA only)
ManufacturerExTox Gasmess-Systeme GmbH

Applications

Facilities with a single gas measuring point — boiler rooms, compressor stations, small technical rooms, cold stores and ammonia installations, fuel and gas stations — wherever a single transmitter is sufficient and investment in a multi-channel control unit would not be justified. Works with ExTox ExSens/Sens transmitters and other transmitters compatible with a 4-20 mA signal.

Frequently asked questions (FAQ)

Does the ET-1D(A) have its own gas sensor?

No — it is a control unit/controller. It receives a 4-20 mA signal from an external transmitter (e.g. from the ExTox ExSens or Sens range) and handles alarming, signalling and the output relays.

What is the difference between the ET-1DA and the ET-1D?

The ET-1DA version additionally has an analogue 4-20 mA output, allowing the measured value to be passed to a higher-level system (e.g. BMS/SCADA). The base ET-1D version does not have this output.

Can the system be expanded with more measuring points in the future?

The ET-1D(A) supports only one channel. Where more measuring points are needed, multi-channel control units from the same family are used (e.g. ET-4D(A), ET-8D(A)).

How is the device mounted?

Four housing variants are available: wall-mount (IP54), DIN-rail, 19" cabinet installation, and panel-mount — the choice depends on the installation location.

Brand & service

The equipment and implementation are in the SafeTech range — selection, delivery, configuration and commissioning of the ExTox gas detection control unit together with the appropriate transmitter (sensor head). We also provide service, certification and periodic inspections of the system.

Why SafeTech

  • 23 years of experience in safety and gas detection (the company has operated since 2003).
  • Selection of the control unit and transmitters to match the number and type of gases measured on site.
  • Installation, commissioning and integration with alarm systems and the BMS.
  • Service, certification and periodic inspections in Suchy Dwór near Gdynia — service across Poland.

Availability & service — Gdynia and Tricity

ExTox ET-1D(A) — gas detection control unit (1 channel) — sales, selection, delivery and service in Gdynia (Suchy Dwór, on the border of Gdynia and the Kosakowo municipality). We serve the Tricity (Gdańsk, Sopot, Gdynia), Rumia, Reda, Wejherowo, the Pomerania region and all of Poland. Ask about pricing and availability.